About the H3C UPS6000-A 40kVA Modular UPS

The H3C UPS6000-A 40kVA Modular UPS accepts three-phase 380/400/415 V AC input (three-phase four-wire) and delivers the same voltage specification at output, supporting input frequency ranges of 40–70 Hz with auto-sensing capability. This enterprise-grade uninterruptible power supply employs double-conversion online (VFI) topology to eliminate transfer time to battery—critical for mission-critical infrastructure where zero switching gaps are non-negotiable. Built on H3C's proven modular architecture, the UPS6000-A-40K features hot-swappable power modules and N+X redundancy support, allowing IT teams to scale capacity and fault tolerance without extended downtime.

The system delivers 40 kVA / 40 kW at 1.0 output power factor with up to 96% efficiency in double-conversion mode. An IGBT-based PWM rectifier achieves input power factor correction of ≥ 0.99 at full load while maintaining input total harmonic distortion (THDi) of ≤ 3%, protecting upstream distribution equipment from harmonic contamination. Output frequency synchronizes to input or runs free-running at 50 Hz or 60 Hz. H3C engineered this unit with forced air cooling and intelligent fan speed control to maintain stable operation across 0°C to 40°C environments. Communication options include RS-485, dry contacts, and optional SNMP network management card integration. Storage architects and IT procurement teams seeking modular, redundant power protection for data centers, server farms, and critical facilities will find the part number UPS6000-A-40K delivers enterprise resilience. Contact Omnixon Global to request a formal quote.

Enterprise Deployment Scenarios

  • Multi-rack data center environments requiring N+X redundancy and zero transfer time to battery backup
  • Modular colocation facilities where capacity must scale incrementally without full-system replacement
  • Regulated server rooms and network operations centers with strict harmonic distortion compliance (≤ 3% THDi)
  • Industrial control and manufacturing sites operating across global input frequencies (40–70 Hz auto-sensing)
  • Mission-critical storage and virtualization infrastructure demanding 96% double-conversion efficiency and hot-swappable module redundancy

Technical Specifications

BrandH3C
CategoryUPS & Power Protection
SKUUPS6000-A-40K
Part NumberUPS6000-A-40K
ConditionNew
Manufacturer Part NumberUPS6000-A-40K
Product SeriesUPS6000-A
UPS TopologyDouble-Conversion Online (VFI)
Rated Capacity40 kVA / 40 kW
Output Power Factor1.0
ArchitectureModular, hot-swappable power modules
Redundancy SupportN+X modular redundancy
Input Voltage3-phase, 380/400/415 V AC (three-phase four-wire)
Output Voltage3-phase, 380/400/415 V AC (three-phase four-wire)
Input Frequency Range40–70 Hz (auto-sensing)
Output Frequency50 Hz or 60 Hz (synchronized to input or free-running)
Rectifier TechnologyIGBT-based PWM rectifier
Input Power Factor Correction≥ 0.99 at full load
Input Total Harmonic Distortion (THDi)≤ 3%
System EfficiencyUp to 96% in double-conversion mode
Transfer Time (to Battery)Zero (online double-conversion, no transfer gap)
Communication InterfacesRS-485, dry contacts, optional SNMP network management card
Operating Temperature0°C to 40°C
Cooling MethodForced air cooling with intelligent fan speed control
Form FactorModular rackmount / floor-standing cabinet
Compliance StandardsIEC 62040-1, IEC 62040-2, IEC 62040-3

Frequently Asked Questions about H3C UPS6000-A 40kVA Modular UPS

How long will this UPS run my load?

Runtime is load-dependent. Most enterprise UPS at 50% load deliver 8-12 minutes battery on standard internal batteries. Add external battery packs (XL / RBC modules) to extend to 30-60 minutes if you need ride-through past short utility blips.

Can it integrate with VMware vCenter / Veeam for graceful shutdown?

Yes — we ship the SNMP / Network Management Card (NMC) alongside the UPS, plus shutdown agents that integrate with VMware PowerChute, Veeam, NetApp ONTAP, and standard SNMP traps for orchestration platforms.

Do you provide installation and battery disposal?

For Dubai and the wider UAE we offer installation, commissioning, and battery recycling per municipality regulations. For broader GCC we partner with local certified electricians and recyclers — included as an option in the quote.

What is the lead time on larger 10-20 kVA models?

Stocked tier (under 10 kVA): 5-7 business days. 10-20 kVA: 2-4 weeks typically. 20+ kVA modular / parallel systems: 6-10 weeks vendor-side, plus on-site commissioning scheduling. Real numbers quoted with every order.